One (1) 3750/4687KVA Standard Oil Filled Transformer. Type ATAB. 3 phase, 60 cycle. Class OA/FA. High voltage: 34,400 Delta, Low voltage: 4160Y/2400. With two (2) 2-1/2% taps above and below. 55°C rise. 5.7% impedance. B.I.L. HV: 200KV, B.I.L. LV: 75KV. Identified by S/N: 168896. Built in 1962.
|
HIGH VOLTAGE CONNECTIONS: |
TAP CHANGER: |
Volts
|
Amps FA Rating
|
Dial
|
Connects
|
36,200 |
74.8 |
A |
1 to 2 |
35,300 |
76.7 |
B |
2 to 3 |
34,400 |
78.7 |
C |
3 to 4 |
33,500 |
80.8 |
D |
4 to 5 |
32,600 |
83.1 |
E |
5 to 6 |
LOW VOLTAGE CONNECTIONS:
|
|
Volts
|
Amps FA Rating
|
4,160 |
650
|
| Approximate Dimensions: |
8'-7"L X 5'-10"W X 12'-5"H (with bushings)
8'-7"L X 5'-10"W X 11'-101/2"H (without bushings)
|
|
| Approximate Shipping Weight: |
35,350 Lbs.
|
|
| IMMEDIATE DEliVERY |
|
|