75,000 #/hr Cleaver Brooks Boiler

Details / Specifications
Capacity75,000 #/hr
Quantity4
ManufacturerNebraska Boiler
AvailabilityImmediate
ModelNOS-2A-67
Burner Manf.TODD or NATCOM
Design Pressure350 psig
Operating Pressures (psig)125-335
Steam Temp. (°F)Saturated
Drum Type2-drum, bent tube type referred to as an "O" design, composed of a 36" I.D. steam drum and a 24" lower drum with 2" O.D. tubes
Code DesignBuilt in accordance with ASME Code and bearing N.B. and H.S.B. stampings.
NOx with FGR30 PPM
FuelNatural Gas / Oil
FanForced draft fan with 100HP TEFC motor, 3/60/480V with starter
Flame Monitoring SystemFireye E100 Microprocessor
Control Circuit Tranformer1/60/120V Included
Valve TrimThe valve trim consists of: (1) 2-1/2" Electronic feedwater control system with 2-1/2" globe bypass valve, (1) 2-1/2" stop valve, (1) 2-1/2" check valve, (1) 1/2" feed control system drain valve, (1) Clark-Reliance LWCO and auxiliary LWCO with bypass, (1) Clark-Reliance water column assembly with high and low alarm, water gauge and valves, tri-cocks and drain valves, (1) 1" continuous blowdown control valve and stop valve, (1) 1" chemical feed valve, (1) 3/4" vent valve, (1) 2" and (1) 2-1/2" Consolidated safety valves, (2) 1-1/2" Edwards blowoff valves, (1) 8-1/2" Ashcroft steam gauge and (1) 4" auxiliary safety connection with blank-off flange, as well as miscellaneous valve trim, regulators, and controllers.
Approx. Dimensions33' - 9" L x 10' - 7" W x 12' - 10" H
Approx. Shipping Weight (lbs.)74,900 lbs
Freight MethodTrailer
More InformationEach boiler has a total heating surface of 6,098 sq. ft., of which 833 sq. ft. are in the waterwalls

Moore Microprocessor combination combustion and single element (convertible to three element) feedwater control system

Burner and controls are metal housed with an extended rainhood cover. (1) 8' high x 48" dia. stack with rectangular to round transition piece is included. All integrally mounted on a drop-deck, triple-axle trailer.