22000 KW Shin Nippon

 

STEAM TURBINE GENERATOR:

 MANUFACTURER:                        SHIN NIPPON MACHINERY COMPANY

 RATING:                                    22000 KW

                                                PRESSURE         TEMPERATURE               FLOW

 INLET STEAM:                           855.5 PSIG        865.4 DEG F                   209,051 LBS/HR

 CONTROLLED STEAM:                233.3 PSIG                                             0 TO 62,382 LBS/HR

 UNCONTROLLED STEAM:           78.1 PSIG                                              35,322 LBS/HR

 EXHAUST STEAM:                      1.74 HGA                                                163,093 LBS/HR

 RATING WITH ZERO EXTRACTION:  20,000 KW

 STEAM RATE:                             8.15 LBS/KWH

 MINIMUM STEAM FLOW:           11,900 LBS/HR

 SPEED:                                     3600 RPM

 INLET STEAM SIZE:                    10"

 AE STEAM SIZE:                         8"

 UNCONTROLLED STEAM SIZE:     10"

 EXHAUST STEAM:                      RECTANGLE 126" X 48"

 GOVERNOR:                              WOODWARD 505E

 MODEL NUMBER:                        C10-R13-E

 ROTATION (STEAM FLOW):        CW

 GENERATOR:

 MANUFACTURER:                       EM

 RATING:                                   23,158 KVA

 VOLTAGE:                                 13800 V, 3 PHASE, 60 HZ

 PF:                                           0.95

 SPEED:                                     3600 RPM

 ARMATURE AMPS:                      969 AMPS

 EXCITER:                                  BRUSHLESS, PMG

 TYPE:                                       TEWAC

 CONDENSER:

 CONDENSER WATER FLOW:         16,000 GPM

 COOLING WATER INLET TEMP.:    68 DEG F

 COOLING WATER OUTLET TEMP.:   87 DEG F

 

 HISTORY OF STEAM TURBINE GENERATOR:

 STEAM TURBINE GENERATOR WAS INSTALLED IN 1990, IN 2000 COMPLETE

 STEAM TURBINE INTERNALS AND GENERATOR WERE REPLACED. IT RAN ONLY

 8500 HOURS SINCE THEN. UNIT IS IN VERY GOOD CONDITION.

 

 WATER TREATMENT SYSTEM:

 AQUATECH TWO STAGE WATER TREATMENT SYSTEM WITH RIVER WATER CLARIFIER, DM PLANT

 ETC.

 

 POWERHOUSEBUILDING WITH CRANE

 

 COOLING TOWER

 

 115 KV SUBSTATION, 13.8 KV SWITCHGEAR, 4160 V MOTOR STARTERS, 480 V MCC,

 BATTERY AND BATTERY CHARGER, UPS.

 

 PLANT HISTORY: START UP 1990 AND OPERATED UNTIL 1998, AFTER THIS DATE THE

 PLANT RAN ONLY ON SHORT TIME POWER SALE AND STEAM SALE AGREEMENT.

Shin Nippon Steam Turbine Generator

Turbine Specifications

Capacity22000
Stages13 Stages
Initial Steam Conditions855 psig / 865°F
Exhaust1.75 HG ABS
Steam Rate170,000 #/Hr
RPM3600 RPM

Reduction Gear

Exciter

Generator

ManufacturerElectric Machinery
Rating23158 KVA
Voltage3/60/13,800V
Amps969
Speed1800 RPM

Condenser

TypeCondensing and Extraction

Other

Also included are:

Available at additional cost:

Approx Shipping Dims:
Approx Shipping Weight:

IMMEDIATELY AVAILABLE