Menu Close

Watertube Boilers

150,000 PPH Boiler Superheat 750

Details / Specifications
Capacity150,000 #/hr
ManufacturerNebraska Boiler
Burner Manf.NATCOM
Design Pressure750psig
Operating Pressures (psig)300-675
Steam Temp. (°F)750
Drum TypeType "A" design, composed of a 48" I.D. steam drum and two (2) 24" O.D. lower drums with 2" O.D. tubes
Code DesignThis boiler was built in accordance with ASME Code and bearing N.B. and H.S.B. stampings
NOx with FGR30 PPM
FuelNatural Gas / Oil
FanForced draft fan with 400HP TEFC motor 3/60/460V, 1800RPM with interconnecting air duct to windbox
Flame Monitoring SystemFireye flame safeguard burner control system, 1/60/110V., I.R., F.M. and U.L. approved
Valve TrimClark-Reliance water column with high and low water alarm, LWCO, and auxiliary bypass valve station, sootblower wall boxes and bearings, feed, stop and check valves, blowoff, vent and drain valves, continuous blowdown control valve, two (2) 2" and one (1) 1.5" Consolidated safety valves, chemical feed valve, 8.5" Ashcroft pressure gauge, as well as miscellaneous valve trim and regulators.
Approx. Dimensions47' - 0" L x 12' -5" W x 16' -6" H
Approx. Shipping Weight (lbs.)210,000 Lbs.
Freight MethodRail
More InformationThe boiler has a total heating surface of 10,535 Sq. ft. of which 1155 Sq. ft. are in the water walls. The furnace volume is 2223 cu. ft. The boiler has a 929 Sq. Ft. drainable, 750°F superheater with 1.5" tubes.

The boiler is completely encased with burner and oil train NEMA IV construction for weather-tight outdoor installation. Boiler will generate a continuous steam capacity of 150,000#/hr. of superheated steam at an operating pressure 250-675 psig at 750°F when supplied with feedwater at 212°F